Blowthrough Detection

A blowthrough (or failed-open) steam trap is one that has failed and is continuously passing steam instead of only releasing condensate. This wastes steam 24/7 until the trap is repaired and can represent significant energy and cost losses.

What Gets Detected​

The Shoplogix IMS platform detects two categories of blowthrough:

ConditionWhat It Means
Suspected BlowthroughContinuous, sustained temperature rise pattern consistent with a trap that has failed open and is passing steam continuously
Intermittent Blowthrough — Heavy/Medium/LightRepeating pattern of excessive steam passage during short intervals; the trap is passing steam at times when it should be closed

How Detection Works​

The platform analyzes the condensate temperature timeseries from your Eversensor. A blowthrough signature is characterized by:

  • A rapid, sustained rise in condensate temperature
  • Temperature maintaining an elevated level rather than cycling normally
  • The pattern repeating or persisting over time (for intermittent blowthrough)

The detection algorithm compares short-term and long-term temperature patterns to identify the characteristic "up and to the right" signature of a failed-open trap. This runs automatically on a scheduled basis — no manual trigger required.

Severity Levels for Intermittent Blowthrough​

When intermittent blowthrough is detected, the platform classifies it by severity:

ConditionWhat It Indicates
Intermittent Blowthrough — HeavyFrequent, high-volume intermittent blowthrough — highest steam loss
Intermittent Blowthrough — MediumModerate frequency and volume
Intermittent Blowthrough — LightInfrequent, lower-volume — monitor and plan inspection

All three levels trigger alerts to subscribed users and appear in the Steam Trap dashboard in Shoplogix IMS.

Responding to a Blowthrough Detection​

  1. Check the cost impact — each failing trap shows an estimated steam loss value. This helps prioritize which traps to repair first when you have multiple failures.
  2. Confirm with a field inspection — the platform detection is probabilistic. A technician should confirm the failure mode before repair.
  3. Record a ground truth measurement — after inspection, you can enter a verified measurement in Insights. Ground truth data helps calibrate and improve future detection. See Ground Truth & Field Measurements.
  4. Repair the trap — once repaired, the trap condition should return to Good automatically as the temperature returns to normal.

Notifications​

Blowthrough events trigger email alerts to users subscribed to blowthrough notifications. For delivery to your own systems, set up a webhook subscription.

Cost Impact​

Blowthrough failures typically have the highest per-trap cost impact because steam passes continuously. The platform calculates estimated dollar value and CO₂ impact from the orifice size and inlet pressure you've configured.

See Cost of Steam Analytics for details.